top of page

Your Solution to Attain a
Protective Environment (PE)
Air Quality and Ventilation Requirements
-
HEPA filtration: High-Efficiency Particulate Air (HEPA) filters capable of removing ≥99.97% of particles ≥0.3 microns.
-
Minimum 12 air changes per hour (ACH): Ensures clean air is circulated frequently.
-
Positive pressure ventilation: Air flows out of the room to prevent outside air (which may carry pathogens) from entering.
-
Sealed room construction: Limits infiltration of unfiltered air through windows, doors, or cracks.